4.4 Article Proceedings Paper

Analysis of Corona Onset Electric Field Considering the Effect of Space Charges

Journal

IEEE TRANSACTIONS ON MAGNETICS
Volume 47, Issue 5, Pages 1390-1393

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TMAG.2010.2081972

Keywords

Corona; electric field; space charge; transmission lines

Funding

  1. Fundamental Research Funds for the Central Universities in China [09MG08]

Ask authors/readers for more resources

A modified method based on the optimized charge simulation method (CSM) is used to predict the corona onset voltage and electric field when the space charges due to the corona are considered. Based on the streamer model of corona discharge, space charges generated near the conductors are predicted. In order to calculate the electric field at the conductor surface, space charges are replaced by some equivalent line charges near the conductor. Because of the existence of space charges, the corona onset electric field is changed a little. After a simplified model of actual power transmission lines is introduced with the help of rough coefficient, the corona onset voltage and corona onset electric field are calculated for different types of conductors finally.