4.7 Article

A New IED With PMU Functionalities For Electrical Substations

Journal

IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT
Volume 62, Issue 12, Pages 3209-3217

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIM.2013.2270921

Keywords

IEC61850; IEEE1588; merging unit; phasor measurement unit; synchronization

Funding

  1. [MIUR 2008TCWC98-PRIN 2008]

Ask authors/readers for more resources

This paper proposes a new distributed architecture to measure synchrophasors in power substations, inspired by the standards IEC 61850. The new scheme is implemented in the process bus, where a high performance merging unit (MU), synchronized by precision time protocol (PTP), according to the standard IEEE 1588-2008, sends the sampled values (SVs) to an intelligent electronic device (IED) enabled to behave as a phasor measurement unit (PMU). The synchrophasors are evaluated in the IED through an algorithm based on the Taylor Fourier Transform and suitably modified to have high performance also in terms of response time in presence of step change conditions. Different tests and considerations are presented to evaluate the various elements of uncertainty that a distributed architecture can introduce and, finally, to ensure the feasibility of the proposed approach.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available