4.6 Article

Evaluation of Differential Pressure Setpoint of Chilled Water Pumps in Clean Room HVAC Systems for Energy Savings in High-Tech Industries

Journal

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS
Volume 49, Issue 3, Pages 1015-1022

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIA.2013.2251992

Keywords

Chilled water pumps; clean room; differential pressure; energy savings; field testing; high-tech industries

Funding

  1. National Science Council of Taiwan [NSC 100-2221-E-022-001, 101-2622-E-022-002-CC3]

Ask authors/readers for more resources

Variable-frequency speed control technologies are widely used in chilled water pumps in clean room heating, ventilation, and air-conditioning (HVAC) systems in high-tech industries to reduce energy consumption. Pumps with variable frequency drivers work based on the reading from the differential pressure sensor placed between the chilled water supply and return lines before the secondary and tertiary pumps. The determination of the differential pressure setpoint must take pipeline topology and material, chilled water flow demand, heat loading, and system equipment aging into account so as to provide operating flexibility for energy conservation while ensuring the secure operation of the clean room. To enhance clean room energy efficiency, a new methodology is proposed in this paper for determining the proper chilled piping pressure setpoint for the pumps. The mathematic model of head loss required for generic secondary and tertiary chilled networks widely used in clean rooms is derived using the Hazen-Williams formula principle. The field testing results confirm the validity of the proposed approach through a practical clean room HVAC system for electronic semiconductor manufacturing, and the energy savings and investment benefits due to the use of the proper differential pressure setpoint are determined.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available