Accurate estimation of the time-of-arrival of partial discharge pulses in cable systems in service

Journal

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TDEI.2008.4591242

Keywords

delay estimation; defect location; partial discharges; power cables; signal analysis

Ask authors/readers for more resources

Accurate location of the origins of partial discharges in power cable systems, based on arrival times, is imperative for the identification and assessment of defects. This paper evaluates different time-of-arrival algorithms in order to determine which method yields most accurate location under different circumstances. These methods are based on trigger level, Akaike Information Criterion, energy criterion, Gabor's signal centroid and phase in frequency domain. Several criteria are defined by which the algorithms are evaluated. These criteria include the sensitivity to noise, pulse shape and effect of load impedance. The sensitivity of the methods upon varying these quantities is evaluated analytically and by means of simulations. Further, the methods are tested on a medium-voltage cable system by injecting PD pulses in a cable with one joint. Each algorithm is applied to the measured pulses and the resulting location is compared with the known joint location. From the results the energy criterion method and the phase method show the best performance.